Since there is no current measurement in SAM600-IO, evaluation of the
following parameters are not possible in the circuit breaker condition
monitoring function (SSCBR):
•
Circuit breaker status
•
Remaining life of the circuit breaker
•
Contact erosion estimation
•
Circuit breaker contact travel time
Ensure that OPENPOS, CLOSEPOS, INVDPOS, CBLIFEAL, IPOWALPH,
IPOWLOPH, TRVTOPAL and TRVTCLAL signals are not used in SAM600–IO.
5.3.3.1
Setting procedure on the IED
GUID-4E895FEA-74BF-4B11-A239-0574F8FF5188 v5
The parameters for breaker monitoring (SSCBR) can be set via Protection and Control Manager
(PCM600).
Common base IED values for primary current (
IBase), primary voltage (UBase) and primary
power (
SBase) are set in Global base values for settings function GBASVAL.
GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.
PhSel: It is used to select different phase values.
IBase: Base phase current in primary A. This current is used as reference for current settings.
InitCounterVal: Initial value for number of operations
InitAccCurrPwr: Initial value for accumulated I^CurrExponent integr over CB open travel time
value.
InitInactDays: Initial value for inactive days.
InactiveAlHrs: Alarm time for inactive days counter in hours.
InitCBRemLife: Initial value for remaining life estimates.
InactiveAlDays: Alarm level for inactive days counter.
OpenTimeCorr: Correction factor for circuit breaker opening travel time.
CloseTimeCorr: Correction factor for circuit breaker closing travel time.
tTrOpenAlm: Setting of alarm level for opening travel time.
tTrCloseAlm: Setting of alarm level for closing travel time.
OperAlmLevel: Alarm limit for number of mechanical operations.
OperLOLevel: Lockout limit for number of mechanical operations.
CurrExponent: Current exponent setting for energy calculation. It varies for different types of
circuit breakers. This factor ranges from
0.5 to 3.0.
AccStopCurr: RMS current setting below which calculation of energy accumulation stops. It is
given as a percentage of
IBase.
ContTrCorr: Correction factor for time difference in auxiliary and main contacts' opening time.
AlmAccCurrPwr: Setting of alarm level for accumulated energy.