4.1.2.1
Three-phase tripping
M14828-7 v10
Connect the inputs from the protection functions to the input TRIN. The TMGAPC function
block is used to combine up to 32 inputs into one output. Connect the output TRIP to the
binary outputs on the IO board.
This signal can also be used for other purposes internally in the IED. An example could be the
starting of breaker failure protection. The three outputs TRL1, TRL2, TRL3 will always be
activated at every trip and can be utilized on individual trip outputs if single-phase operating
devices are available on the circuit breaker even when a three-phase tripping scheme is
selected.
Set the function block to
Program = 3 phase and set the required length of the trip pulse to for
example,
tTripMin = 150ms.
The typical connection is shown below in figure
.
BLOCK
BLKLKOUT
TRIN
TRINL1
TRINL2
TRINL3
PSL1
PSL2
PSL3
1PTRZ
1PTREF
P3PTR
SETLKOUT
RSTLKOUT
STDIR
TRIP
SMPPTRC
TRL1
TRL2
TRL3
TR1P
TR2P
TR3P
CLLKOUT
START
STL1
STL2
STL3
FW
REV
Protection functions with 3 phase
trip, for example time delayed
overcurrent protection
TMAGAPC
STN
IEC05000544-4-en.vsdx
IEC05000544 V4 EN-US
Figure 4:
Tripping logic SMPPTRC is used for a simple three-phase tripping application
4.1.2.2
Single- and/or three-phase tripping
M14828-11 v7
The single-/three-phase tripping operation mode will give single-phase tripping for single-
phase faults and three-phase tripping for multi-phase fault. This operating mode is always
used together with a single-phase autoreclosing scheme.
The single-phase tripping operation mode can include different options and the use of the
different inputs in the function block. Inputs TRINL1, TRINL2 and TRINL3 shall be used for trip
signals from functions with built-in phase selection logic such as distance or line differential
protection functions.
The inputs 1PTRZ and 1PTREF are used for single-phase tripping from functions which do not
have built-in phase selection logic:
•
1PTRZ can be connected to the carrier aided trip signal from the distance protection
scheme (it means that another distance protection function has seen or detected the
fault)
•
1PTREF can be connected to an earth fault function such as EF4PTOC or a carrier aided
trip signal from the earth fault protection scheme
Section 4
1MRK 511 445-UEN B
Logic
28
Switchgear control unit SAM600-IO
Application manual