Refer to Table
for the description of the input-output relationship in terms of the value and
the quality attributes.
Table 4:
Description of the input-output relationship
VALID
OPEN
CLOSE
POSITION
Value
Description
0
-
-
0
Intermediate
1
0
0
0
Intermediate
1
1
0
1
Open
1
0
1
2
Closed
1
1
1
3
Bad State
3.4.3
Setting guidelines
SEMOD55398-5 v5
The function does not have any parameters available in the PCM600.
3.5
Single point generic control 8 signals SPC8GAPC
SEMOD176448-1 v3
3.5.1
Identification
SEMOD176456-2 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Single point generic control 8 signals
SPC8GAPC
-
-
3.5.2
Application
SEMOD176511-4 v7
The Single point generic control 8 signals (SPC8GAPC) function block is a collection of 8 single
point commands that can be used for direct commands for example putting IED in
"ChangeLock" state from remote. In this way, simple commands can be sent directly to the IED
outputs, without confirmation. Confirmation (status) of the result of the commands is
supposed to be achieved by other means, such as binary inputs and SPGAPC function blocks.
PSTO is the universal operator place selector for all control functions. Even if
PSTO can be configured to allow LOCAL or ALL operator positions, the only
functional position usable with the SPC8GAPC function block is REMOTE.
3.5.3
Setting guidelines
SEMOD176518-4 v7
The parameters for the single point generic control 8 signals (SPC8GAPC) function are set via
PCM600.
Operation: turning the function operation On/Off.
There are two settings for every command output (totally 8):
PulseModex: decides if the command signal for output x is Latched (steady) or Pulsed.
1MRK 511 445-UEN B
Section 3
Control
Switchgear control unit SAM600-IO
25
Application manual