![ABB Relion SAM600 Скачать руководство пользователя страница 41](http://html.mh-extra.com/html/abb/relion-sam600/relion-sam600_applications-manual_2830041.webp)
Name of input
Type
Default
Description
Value when
activated
Value when
deactivated
IN1
BOOLEAN
0
Input 1
1
0
IN2
BOOLEAN
0
Input 2
2
0
IN3
BOOLEAN
0
Input 3
4
0
IN4
BOOLEAN
0
Input 4
8
0
IN5
BOOLEAN
0
Input 5
16
0
IN6
BOOLEAN
0
Input 6
32
0
IN7
BOOLEAN
0
Input 7
64
0
IN8
BOOLEAN
0
Input 8
128
0
IN9
BOOLEAN
0
Input 9
256
0
IN10
BOOLEAN
0
Input 10
512
0
IN11
BOOLEAN
0
Input 11
1024
0
IN12
BOOLEAN
0
Input 12
2048
0
IN13
BOOLEAN
0
Input 13
4096
0
IN14
BOOLEAN
0
Input 14
8192
0
IN15
BOOLEAN
0
Input 15
16384
0
IN16
BOOLEAN
0
Input 16
32768
0
The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are
active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an
integer by the B16I function block.
4.9
Boolean to integer conversion with logical node
representation, 16 bit BTIGAPC
SEMOD175753-1 v4
4.9.1
Identification
SEMOD175757-2 v5
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean to integer conversion with
logical node representation, 16 bit
BTIGAPC
-
-
4.9.2
Application
SEMOD175849-4 v6
Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC) is used to
transform a set of 16 binary (logical) signals into an integer. BTIGAPC has a logical node
mapping in IEC 61850.
The BTIGAPC function will transfer a combination of up to 16 binary inputs INx where 1≤x≤16 to
an integer. Each INx represents a value according to the table below from 0 to 32768. This
follows the general formula: INx = 2
x-1
where 1≤x≤16. The sum of all the values on the activated
INx will be available on the output OUT as a sum of the values of all the inputs INx that are
activated. OUT is an integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 it
corresponds to that integer 65535 is available on the output OUT. BTIGAPC function is
1MRK 511 445-UEN B