max
2
min
8
.
0
P
U
RLd
IECEQUATION15051 V1 EN-US
(Equation 16)
Where,
P
max
is the maximum exporting power
U
min
is the minimum voltage for which P
max
can occur
0.8 is security factor.
ArgLd
: This is used to set the load angle determining the load impedance area of
the load discrimination characteristic. Set the parameter to the maximum possible
load angle at maximum possible load. The default value is set at 30 deg.
OpModeI0
: This is used to select the operation
On
or
Off
of the end zone timer
logic using residual overcurrent start to provide a remote backup.
OpModetEnd1
: It is used to select operation
On
or
Off
of the end zone 1.
OpDirEnd1
: This is used to select the direction mode of end zone 1. It can be set to
Non-directional
,
Forward
and
Reverse
. It is recommended to set as
Forward
.
tEnd1
: This is used to set time delay for the first stage remote backup. The setting
should allow the farthest zone to operate. The default setting is 2.5s.
OpModetEnd2
: This is used to select the operation
On
or
Off
of the end zone 2.
OpDirEnd2
: This is used to select the direction mode of the end zone 2. It can be
set to
Non-directional
,
Forward
and
Reverse
. It is recommended to set this as
Non-
directional
.
tEnd2
: This is used to set the time delay for the second stage trip. It should be set in
coordination with the
tEnd1
timer. The default setting is 3.0s.
OpModeGenSt
: This is used to select
On
or
Off
of zone timers start by general start
signal. The default value is
Off
.
ZoneCharSym
: This is used to select measuring zone
Symmetry/Nonsymmetry
around R – X plane and it is set by default to
Symmetry
. With this default value, it
is not possible to set resistive and reactance reaches in reverse direction. However,
if it is needed to specify the reverse reaches depending on the application, it is
recommended to set this parameter to
Nonsymmetry
.
Start
GUID-D2A63BD2-34EA-407C-B43F-165DCB576C4E v2
CharStartZ<
: It is used to select the underimpedance start characteristic (i.e.
Circular
and
Quadrilateral
).
Z1CircleStart
: This is used to set a positive sequence impedance reach in Ohm of
the starting element circular characteristic. It will be set to operate for all faults
1MRK 506 375-UEN A
Section 7
Impedance protection
Railway application RER670 2.2 IEC
115
Application manual
Содержание RELION RER670
Страница 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 48: ...42 ...
Страница 70: ...64 ...
Страница 80: ...74 ...
Страница 100: ...94 ...
Страница 210: ...204 ...
Страница 364: ...358 ...
Страница 384: ...378 ...
Страница 468: ...462 ...
Страница 494: ...488 ...
Страница 504: ...498 ...
Страница 505: ...499 ...