basic time
tGL2
, the
UL1E
will be checked against a set limit
UL1E < U0Min
at
the end of 100ms after the reset of starting element.
The basic time
tGL2
is effective only during the underimpedance or residual
overcurrent start. If the voltage
UL1E
is greater than the set limit
U0Min
, the start
signal is maintained. A trip will occur if the voltage
UL1E
does not fall below the
set limit by the end of extra time
t1L2
to
t6L2
that are assigned to the respective
zones.
ModePhPref
: In compensated earthed systems, phase L2 will be specially treated.
Two operation modes i.e.
Equal priority
and
L1 before L2
of phase preference
variants are implemented. The default is set to
Equal priority
.
OpModet0L2
: This is used for
Off/On
operation of the
t0L2
timer if phase
preference is set.
t0L2
: This is an additional time delay to the trip phase L2 in stub line.
OpModet1L2
: This is used for
Off/On
operation of the
t1L2
timer if phase
preference is selected. The default setting is
On
.
t1L2
: This is an additional time delay to trip phase L2 if the phase preference is set
to trip phase L2 in zone 1. The default setting is 1.5s.
OpModet2L2
: This is used for
Off/On
operation of the
t2L2
timer if phase
preference is selected. The default setting is
Off
.
t2L2
: This is an additional time delay to trip phase L2 if the phase preference is set
to trip phase L2 in zone 2. The default setting is 2.5s.
OpModet3L2
: This is used for
Off/On
operation of the
t3L2
timer if phase
preference is selected. The default setting is
Off
.
t3L2
: This is an additional time delay to trip phase L2 if the phase preference is set
to trip phase L2 in zone 3. The default setting is 0.0s.
OpModet4L2
: This is used for
Off/On
operation of the
t4L2
timer if phase
preference is selected. The default setting is
Off
.
t4L2
: This is an additional time delay to trip phase L2 if the phase preference is set
to trip phase L2 in zone 4. The default setting is 0.0s.
OpModet5L2
: This is used for
Off/On
operation of the
t5L2
timer if phase
preference is selected. The default setting is
Off
.
t5L2
: This is an additional time delay to trip phase L2 if the phase preference is set
to trip phase L2 in zone 5. The default setting is 0.0s.
OpModet6L2
: This is used for
Off/On
operation of the
t6L2
timer if phase
preference is selected. The default setting is
Off
.
Section 7
1MRK 506 375-UEN A
Impedance protection
112
Railway application RER670 2.2 IEC
Application manual
Содержание RELION RER670
Страница 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 48: ...42 ...
Страница 70: ...64 ...
Страница 80: ...74 ...
Страница 100: ...94 ...
Страница 210: ...204 ...
Страница 364: ...358 ...
Страница 384: ...378 ...
Страница 468: ...462 ...
Страница 494: ...488 ...
Страница 504: ...498 ...
Страница 505: ...499 ...