HV side: IL1=I
V
; IL2=I
U
LV side: IL1=I
S
, IL2= 0
Settings within the transformer differential protection:
PhSelW1
=
(IL1-IL2)/2
PhSelW2
=
IL1
InvW2Curr
=
No
Solution 2
for CT connections and ACT configuration):
Connection to the preprocessing blocks:
HV side: IL1=I
U
; IL2=I
V
LV side: IL1=0, IL2= I
S
Settings within the transformer differential protection:
PhSelW1
=
(IL1-IL2)/2
PhSelW2
=
IL2
InvW2Curr
=
Yes
Base current
The base current is calculated for each side (winding 1 and winding 2) of the power
transformer:
1
1000
1
121
W
SBase
IBaseW
A
UBase
IECEQUATION16075 V1 EN-US
(Equation 4)
2
1000
2
1067
W
SBase
IBaseW
A
UBase
IECEQUATION16076 V1 EN-US
(Equation 5)
where:
SBase
Rated power of transformer [MVA]
UBase
W1
Rated phase-to-phase voltage of winding 1 [kV]
UBase
W2
Rated phase-to-phase voltage of winding 2 [kV]
The base currents for T1PPDIF functions are set under Global Base Values in
Parameter Setting tool.
Section 6
1MRK 506 375-UEN A
Differential protection
84
Railway application RER670 2.2 IEC
Application manual
Содержание RELION RER670
Страница 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 48: ...42 ...
Страница 70: ...64 ...
Страница 80: ...74 ...
Страница 100: ...94 ...
Страница 210: ...204 ...
Страница 364: ...358 ...
Страница 384: ...378 ...
Страница 468: ...462 ...
Страница 494: ...488 ...
Страница 504: ...498 ...
Страница 505: ...499 ...