LEModeZ3
: This is used to operate the load discrimination characteristic of zone 3.
Set this to
On
.
LCModeZ3
: This is used to enable/disable load compensation mode for zone 3. Set
this to
Off
.
X1FwZ3
: This is used to set the forward positive sequence reactance reach for zone
3 in Ohm/p. This should be set to 120% of reactance of (Line 1 + Line 2).
Therefore, set
X1FwZ3
to 1.2 x (50 +100) x 0.112 = 20.16 Ohm.
REoverRLZ3
: This is used to provide zero sequence compensation for phase-to-
earth faults.
28
.
0
1
097
.
0
151
.
0
2
1
1
2
1
1
0
R
R
R
R
L
E
IECEQUATION15052 V1 EN-US
(Equation 23)
Therefore, set this to 0.28.
XEoverXLZ3
: This is used to provide zero sequence compensation for phase-to-
earth faults.
83
.
0
1
112
.
0
298
.
0
2
1
1
2
1
1
0
X
X
X
X
L
E
IECEQUATION15053 V1 EN-US
(Equation 24)
Therefore, set this to 0.83.
RFPEFwZ3
: This may be set identical to setting
RFPEFwZ2
which is 40.13 Ohm.
RFPPFwZ3
: This may be set identical to setting
RFPEFwZ3
which is 40.13 Ohm.
TimerSelZ3
: This is used for Zone timer selection mode of zone 3. Set this to
Timers separated
.
OpModetPEZ3
: Set this to
On
.
tPEZ3
: Choose a time delay for zone 3 with a margin to assure selectivity to zone 2
of adjacent lines. A delay time difference of 0.4s between the zones is sufficient.
The time delay for zone 3 therefore can be set to 0.8s.
OpModetPPZ3
: Set this to
On
.
tPPZ3
: Set this identical to
tPPZ3
= 0.8s.
Zones 4, 5 and 6 can be set on similar lines based on the
application.
1MRK 506 375-UEN A
Section 7
Impedance protection
Railway application RER670 2.2 IEC
141
Application manual
Содержание RELION RER670
Страница 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 48: ...42 ...
Страница 70: ...64 ...
Страница 80: ...74 ...
Страница 100: ...94 ...
Страница 210: ...204 ...
Страница 364: ...358 ...
Страница 384: ...378 ...
Страница 468: ...462 ...
Страница 494: ...488 ...
Страница 504: ...498 ...
Страница 505: ...499 ...