tPPZ1
: This is used to set the time delay to trip for phase-to-phase faults in zone 1.
The default setting is 0.0s.
Zone 2
GUID-DD64B7C1-6337-4AC5-995C-8C068E1E379D v2
OpZ2
: This is used for the
Off/On
operation of zone 2 and it is set to
Off
by default.
DirModeZ2
: This is used to set the zone 2 direction mode. It can be set to
Non-
directional
,
Forward
and
Reverse
. The
Forward
direction mode is set by default.
PhSelModeZ2
: This is used to enable the measuring loops of zone 2. It can be set to
Phsel logic
,
Release L1E
,
ReleaseL2E
,
Release PE
,
Release L1L2
and
Release
PE&PP
modes. The default setting is
Phsel logic
mode.
LEModeZ2
: This is used to operate the load discrimination characteristic of zone 2.
The default setting is
Off
.
LCModeZ2
: This is used to enable/disable the adaptive load compensation mode of
zone 2. It avoids overreaching of the zone in to the next section in case of resistive
fault due to remote end feed. Generally, this setting is not needed for zone 2. The
default setting is
Off
.
X1FwZ2
: This is used to set the forward positive sequence reactance reach of zone
2 in Ohm/p. The zone should never underreach the next section. The recommended
setting is 120% of the protected line length. Impact of the mutual coupling should
be considered for the double circuit lines.
X1RvZ2
: This is used to set the reverse positive sequence impedance reach of zone
2 in Ohm/p. It may be set identical to
X1FwZ2
.
REoverRLZ2
: This is used to set the earth return compensation factor for resistance
of zone 2. It provides zero sequence compensation for phase-to-earth faults.
XEoverXLZ2
: This is used to set the earth return compensation factor for reactance
of zone 2. It provides zero sequence compensation for phase-to-earth faults.
RFPEFwZ2
: This is used to set the forward fault resistive reach in Ohm/p for the
phase-to-earth faults in zone 2. This may be set identical to zone 1 setting. In case
of permissive overreach schemes used for short lines, this has to be set higher than
zone 1 resistive reach.
RFPERvZ2
: This is used to set the reverse fault resistive reach in Ohm/p for phase-
to-earth faults in zone 2. This may be set identical to zone 1 setting.
RFPPFwZ2
: This is used to set the forward fault resistive reach in Ohm/p for
phase-to-phase faults in zone 2. This may be set identical to zone 1 setting.
RFPPRvZ2
: This is used to set the reverse fault resistive reach in Ohm/p for phase-
to-phase faults in zone 2. This may be set identical to zone 1 setting.
TimerSelZ2
: This is used to set the zone timer selection mode of zone 2. i.e.
Timers
separated
,
Timers linked
,
General start
,
PhSel start
,
Internal start
and
External
start
. The default setting is
Timers separated
.
1MRK 506 375-UEN A
Section 7
Impedance protection
Railway application RER670 2.2 IEC
129
Application manual
Содержание RELION RER670
Страница 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 48: ...42 ...
Страница 70: ...64 ...
Страница 80: ...74 ...
Страница 100: ...94 ...
Страница 210: ...204 ...
Страница 364: ...358 ...
Страница 384: ...378 ...
Страница 468: ...462 ...
Страница 494: ...488 ...
Страница 504: ...498 ...
Страница 505: ...499 ...