: This is used to set the forward fault resistive reach in Ohm/p for
phase-to-phase faults in zone 4. This may be set identical to
RFPPRVZ4
.
RFPPRvZ4
: This is used to cover the zone 4 fault resistive reach in Ohm/p for
phase-to-phase faults in reverse direction. It should cover apparent phase-to-phase
bus fault resistance allowing for multiple infeed from other circuits. Therefore, it
should be set identical to zone 3 resistive reach setting.
TimerSelZ4
: This is used to set the zone timer selection mode of zone 4. i.e.
Timers
separated
,
Timers linked
,
General start
,
PhSel start
,
Internal start
and
External
start
. The default setting is
Timers separated
.
OpModetPEZ4
: This is used to set the
Off/On
operation of the phase-to-earth timer
of zone 4. The default setting is
Off
.
tPEZ4
: This is used to set the time delay to trip for phase-to-earth faults in zone 4.
It should be set identical to zone 2 timer setting.
OpModetPPZ4
: This is used to set the
Off/On
operation of the phase-to-phase timer
of zone 4. The default setting is
Off
.
tPPZ4
: This is used to set the time delay to trip for phase-to-phase faults in zone 4.
It should be set identical to zone 2 timer setting.
Zone 5
GUID-B9AD6153-0B91-4C1C-AAE1-E387AAC02A98 v2
OpZ5
: This is used for the
Off/On
operation of zone 5 and it is set to
Off
by default.
This Zone can be used for the permissive overreach scheme along with a
communication channel.
DirModeZ5
: This is used to set the zone 5 direction mode. It can be set to
Non-
directional
,
Forward
and
Reverse
. The default setting is
Forward
direction mode.
PhSelModeZ5
: This is used to enable the measuring loops of zone 5. It can be set to
Phsel logic
,
Release L1E
,
ReleaseL2E
,
Release PE
,
Release L1L2
and
Release
PE&PP
modes. The default setting is
Phsel logic
mode.
LEModeZ5
: This is used to operate the load discrimination characteristic of zone 5.
The default setting is
Off
.
LCModeZ5
: This is used to enable/disable the adaptive load compensation mode of
zone 5. It avoids overreaching of the zone in to the next section in case of resistive
fault due to remote end feed. Generally, this setting is not needed for zone 5. The
default setting is
Off
.
X1FwZ5
: This is used to set the forward positive sequence reactance reach of zone
5 in Ohm/p. It may be set identical to either zone 2 or zone 3 reach settings.
X1RvZ5
: This is used to set the reverse positive sequence impedance reach of zone
5 in Ohm/p. It may be set identical to
X1FwZ5
.
REoverRLZ5
: This is used to set the earth return compensation factor for resistance
of zone 5. It provides zero sequence compensation for phase-to-earth faults.
Section 7
1MRK 506 375-UEN A
Impedance protection
108
Railway application RER670 2.2 IEC
Application manual
Содержание RELION RER670
Страница 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 48: ...42 ...
Страница 70: ...64 ...
Страница 80: ...74 ...
Страница 100: ...94 ...
Страница 210: ...204 ...
Страница 364: ...358 ...
Страница 384: ...378 ...
Страница 468: ...462 ...
Страница 494: ...488 ...
Страница 504: ...498 ...
Страница 505: ...499 ...