•
SYNCH signal on the MUx function block indicates that protection functions
are blocked due to loss of internal time synchronization to the IED (that is loss
of the hardware
synchSrc
).
•
MUSYNCH signal on the MUx function block monitors the synchronization
flag
smpSynch
in the datastream and IED hardware time synchronization.
No time synchronization
This example is not valid when GPS time is used for differential
protection, when PTP is enabled or when the PMU report is used.
IEC/UCA 61850-9-2LE
Data
MU
IED
IEC10000075=2=en=Original.vsd
IEC10000075 V2 EN-US
Figure 184:
Setting example without time synchronization
It is also possible to use IEC/UCA 61850-9-2LE communication without time
synchronization.
Settings on the local HMI under
Main menu/Configuration/Time/
Synchronization/TIMESYNCHGEN:1/IEC61850-9-2
:
•
HwSyncSrc
: set to
Off
•
SyncLostMode
: set to
No block
to indicate that protection functions are not
blocked
•
SyncAccLevel
: set to
unspecified
Two status monitoring signals with no time synchronization:
1MRK 506 375-UEN A
Section 18
Station communication
Railway application RER670 2.2 IEC
437
Application manual
Содержание RELION RER670
Страница 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 48: ...42 ...
Страница 70: ...64 ...
Страница 80: ...74 ...
Страница 100: ...94 ...
Страница 210: ...204 ...
Страница 364: ...358 ...
Страница 384: ...378 ...
Страница 468: ...462 ...
Страница 494: ...488 ...
Страница 504: ...498 ...
Страница 505: ...499 ...