RetripMode
FunctionMode
Description
No CBPos Check
Current
re-trip is done without check of
current level
Contact
re-trip is done without check of
auxiliary contact position
Current/Contact
re-trip is done without check of
current level or auxiliary contact
position
IP>
: Current level for detection of breaker failure, set in % of
IBase
. This
parameter should be set so that faults with small fault current can be detected. The
setting can be chosen in accordance with the most sensitive protection function to
start the breaker failure protection. Typical setting is 10% of
IBase
.
I>BlkCont
: If contact based detection for breaker failure is used, this feature can be
blocked if any phase current is larger than this setting level. If the
FunctionMode
is
set
Current/Contact
breaker failure for high current faults are safely detected by the
current measurement function. To increase security the contact based measurement
should be enabled only for small currents. The setting can be given within the
range 5 – 200% of
IBase
.
t1
: Time delay of the re-trip. The setting can be given within the range 0 – 60s in
steps of 0.001 s. Typical setting is 0 – 50ms.
t2
: Time delay of the back-up trip. The choice of this setting is made as short as
possible at the same time as unwanted operation must be avoided. Typical setting is
90 – 200ms (also dependent of re-trip timer).
The minimum time delay for the re-trip can be estimated as:
_
2
1
³ +
+
+
cbopen
BFP reset
margin
t
t
t
t
t
EQUATION1430 V1 EN-US
(Equation 57)
where:
t
cbopen
is the maximum opening time for the circuit breaker
t
BFP_reset
is the maximum time for breaker failure protection to detect correct breaker function (the
current criteria reset)
t
margin
is a safety margin
It is often required that the total fault clearance time shall be less than a given
critical time. This time is often dependent of the ability to maintain transient
stability in case of a fault close to a power plant.
1MRK 506 375-UEN A
Section 8
Current protection
Railway application RER670 2.2 IEC
189
Application manual
Содержание RELION RER670
Страница 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 48: ...42 ...
Страница 70: ...64 ...
Страница 80: ...74 ...
Страница 100: ...94 ...
Страница 210: ...204 ...
Страница 364: ...358 ...
Страница 384: ...378 ...
Страница 468: ...462 ...
Страница 494: ...488 ...
Страница 504: ...498 ...
Страница 505: ...499 ...