Information about the control location is given to TR1ATCC or TR8ATCC
function through connection of the Permitted Source to Operate (PSTO) output of
the QCBAY function block to the input PSTO of the TR1ATCC or TR8ATCC
function block.
Control Mode
SEMOD159053-35 v4
The control mode of the automatic voltage control for tap changer function,
TR1ATCC for single control and TR8ATCC for parallel control can be:
•
Manual
•
Automatic
The control mode can be changed from the local location via the command menu
on the local HMI under
Main menu/Control/Commands/
TransformerVoltageControl(ATCC,90)/TR1ATCC:x/TR8ATCC:x
, or changed
from a remote location via binary signals connected to the MANCTRL,
AUTOCTRL inputs on TR1ATCC or TR8ATCC function block.
Measured Quantities
SEMOD159053-61 v4
In normal applications, the LV side of the transformer is used as the voltage
measuring point. If necessary, the LV side current is used as load current to
calculate the line-voltage drop to the regulation point.
Automatic voltage control for tap changer, TR1ATCC for single control and
TR8ATCC for parallel control function block has three inputs I3P1, I3P2 and U3P2
corresponding to HV-current, LV-current and LV-voltage respectively. These
analog quantities are fed to the IED via the transformer input module, the Analog
to Digital Converter and thereafter a Pre-Processing Block. In the Pre-Processing
Block, a great number of quantities for example, phase-to-phase analog values,
sequence values, max value in a three phase group etc., are derived. The different
function blocks in the IED are then “subscribing” on selected quantities from the
pre-processing blocks. In case of TR1ATCC or TR8ATCC, there are the following
possibilities:
SEMOD159053-65 v6
•
I3P1 represents a three-phase group of phase current with the highest current
in any of the three phases considered. As only the highest of the phase current
is considered, it is also possible to use one single-phase current as well as two-
phase currents. In these cases, the currents that are not used will be zero.
•
For I3P2 and U3P2 the setting alternatives are: any individual phase current/
voltage, as well as any combination of phase-phase current/voltage or the
positive sequence current/voltage. Thus, single-phase as well as, phase-phase
or three-phase feeding on the LV-side is possible but it is commonly selected
for current and voltage.
Section 12
1MRK 506 375-UEN A
Control
290
Railway application RER670 2.2 IEC
Application manual
Содержание RELION RER670
Страница 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 48: ...42 ...
Страница 70: ...64 ...
Страница 80: ...74 ...
Страница 100: ...94 ...
Страница 210: ...204 ...
Страница 364: ...358 ...
Страница 384: ...378 ...
Страница 468: ...462 ...
Страница 494: ...488 ...
Страница 504: ...498 ...
Страница 505: ...499 ...