A request initiates to reserve other bays to prevent simultaneous operation.
•
Actual position inputs for interlocking information are read and evaluated if
the operation is permitted.
•
The synchrocheck/synchronizing conditions are read and checked, and
performs operation upon positive response.
•
The blocking conditions are evaluated
•
The position indications are evaluated according to given command and its
requested direction (open or closed).
The command sequence is supervised regarding the time between:
•
Select and execute.
•
Select and until the reservation is granted.
•
Execute and the final end position of the apparatus.
•
Execute and valid close conditions from the synchrocheck.
At error the command sequence is cancelled.
The switch controller is not dependent on the type of switching device SXCBR or
SXSWI. The switch controller represents the content of the SCSWI logical node
(according to IEC 61850) with mandatory functionality.
12.3.1.3
Switches SXCBR/SXSWI
M16602-3 v6
Switches are functions used to close and interrupt an ac power circuit under normal
conditions, or to interrupt the circuit under fault, or emergency conditions. The
intention with these functions is to represent the lowest level of a power-switching
device with or without short circuit breaking capability, for example, circuit
breakers, disconnectors, earthing switches etc.
The purpose of these functions is to provide the actual status of positions and to
perform the control operations, that is, pass all the commands to the primary
apparatus via output boards and to supervise the switching operation and position.
Switches have the following functionalities:
•
Local/Remote switch intended for the switchyard
•
Block/deblock for open/close command respectively
•
Update block/deblock of position indication
•
Substitution of position indication
•
Supervision timer that the primary device starts moving after a command
•
Supervision of allowed time for intermediate position
•
Definition of pulse duration for open/close command respectively
The realizations of these functions are done with SXCBR representing a circuit
breaker and with SXSWI representing a circuit switch that is, a disconnector or an
earthing switch.
1MRK 506 375-UEN A
Section 12
Control
Railway application RER670 2.2 IEC
243
Application manual
Содержание RELION RER670
Страница 1: ...RELION 670 SERIES Railway application RER670 Version 2 2 IEC Application manual ...
Страница 2: ......
Страница 22: ...16 ...
Страница 48: ...42 ...
Страница 70: ...64 ...
Страница 80: ...74 ...
Страница 100: ...94 ...
Страница 210: ...204 ...
Страница 364: ...358 ...
Страница 384: ...378 ...
Страница 468: ...462 ...
Страница 494: ...488 ...
Страница 504: ...498 ...
Страница 505: ...499 ...