SCSWI
SELECTED
RES_EXT
+
IED
BI
BO
IED
BI
BO
OR
Other SCSWI in the bay
en05000118.vsd
IEC05000118 V2 EN-US
Figure 81:
Application principles for reservation with external wiring
can also be realized over the station bus according to the
application example in Figure
do not
have the same high security compared to the solution in Figure
a higher availability, since no acknowledgment is required.
SCSWI
SELECTED
RES_EXT
IED
IED
OR
Other SCWI in
the bay
Station bus
. . .
SPGAPC
IN
RESGRANT
IntlReceive
. .
.
. .
.
RESGRANT
IntlReceive
IEC05000178-3-en.vsd
IEC05000178 V3 EN-US
Figure 82:
Application principle for an alternative reservation solution
12.3.2
Interaction between modules
M16626-3 v8
A typical bay with apparatus control function consists of a combination of logical
nodes or functions that are described here:
Section 12
1MRK 506 375-UEN A
Control
248
Railway application RER670 2.2 IEC
Application manual