Table 383:
VMMXU Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
UL12HiHiLim
0.0 - 200.0
%UB
0.1
150.0
High High limit in % of UBase
UL12HiLim
0.0 - 200.0
%UB
0.1
120.0
High limit in % of UBase
UL12LowLim
0.0 - 200.0
%UB
0.1
80.0
Low limit in % of UBase
UL12LowLowLim
0.0 - 200.0
%UB
0.1
60.0
Low Low limit in % of UBase
UAmpComp100
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate voltage at
100% of Ur
UL12LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common
for all limits
UL23HiHiLim
0.0 - 200.0
%UB
0.1
150.0
High High limit in % of UBase
UL23HiLim
0.0 - 200.0
%UB
0.1
120.0
High limit in % of UBase
UL23LowLim
0.0 - 200.0
%UB
0.1
80.0
Low limit in % of UBase
UL23LowLowLim
0.0 - 200.0
%UB
0.1
60.0
Low Low limit in % of UBase
UL23LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common
for all limits
UL31HiHiLim
0.0 - 200.0
%UB
0.1
150.0
High High limit in % of UBase
UL31HiLim
0.0 - 200.0
%UB
0.1
120.0
High limit in % of UBase
UL31LowLim
0.0 - 200.0
%UB
0.1
80.0
Low limit in % of UBase
UL31LowLowLim
0.0 - 200.0
%UB
0.1
60.0
Low Low limit in % of UBase
UL31LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common
for all limits
PID-6736-SETTINGS v3
Table 384:
CMSQI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
3I0DbRepInt
1 - 100000
Type
1
10
Cycl: Report interval (s), Db: In 0,001%
of range, Int Db: In 0,001%s
3I0ZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in
0,001% of range
3I0Min
0.0 - 500.0
%IB
0.1
50.0
Minimum value in % of IBase
3I0Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
3I0RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
-
Cyclic
Reporting type
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base
Value groups
3I0LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common
for all limits
3I0AngDbRepInt
1 - 100000
s
1
10
Cyclic report interval (s)
Operation
Off
On
-
-
Off
Operation Mode On / Off
Table continues on next page
1MRK 506 382-UEN A
Section 14
Monitoring
Line distance protection REL650 2.2 IEC
543
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...