Name
Values (Range)
Unit
Step
Default
Description
IL3Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
IL3RepTyp
Cyclic
Deadband
Int deadband
Db & Cyclic 5s
Db & Cyclic 30s
Db & Cyclic 1min
-
-
Cyclic
Reporting type
IL3AngDbRepInt
1 - 100000
s
1
10
Cyclic report interval (s)
Table 381:
CMMXU Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
IL1ZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in
0,001% of range
IL1HiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
IL1HiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
IAmpComp5
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate current at
5% of Ir
IAmpComp30
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate current at
30% of Ir
IL1LowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
IL1LowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
IAmpComp100
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate current at
100% of Ir
IAngComp5
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 5% of Ir
IAngComp30
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 30% of Ir
IAngComp100
-10.000 - 10.000
Deg
0.001
0.000
Angle calibration for current at 100% of Ir
IL1LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common
for all limits
IL2ZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in
0,001% of range
IL2HiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
IL2HiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
IL2LowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
IL2LowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
IL2LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common
for all limits
IL3ZeroDb
0 - 100000
m%
500
1000
Magnitude zero point clamping in
0,001% of range
IL3HiHiLim
0.0 - 500.0
%IB
0.1
150.0
High High limit in % of IBase
IL3HiLim
0.0 - 500.0
%IB
0.1
120.0
High limit in % of IBase
IL3LowLim
0.0 - 500.0
%IB
0.1
80.0
Low limit in % of IBase
IL3LowLowLim
0.0 - 500.0
%IB
0.1
60.0
Low Low limit in % of IBase
IL3LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range, common
for all limits
1MRK 506 382-UEN A
Section 14
Monitoring
Line distance protection REL650 2.2 IEC
541
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...