6.5.7
Technical data
GUID-42119BFF-1756-431C-A5A1-0AB637213E96 v1
Table 63:
PPL2PHIZ technical data
Function
Range or value
Accuracy
Operate value, phase-to-phase
and phase-to-neutral
undervoltage
(1 - 100)% of UBase
±0.5% of U
r
Reset ratio, undervoltage
< 105%
-
Operate value, residual voltage
(5 - 300)% of UBase
±0.5% of U
r
at U
≤ U
r
±0.5% of U at U >
U
r
Reset ratio, residual voltage
> 95%
-
Operate value, residual current
(10 - 200)% of IBase
±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Reset ratio, residual current
> 95%
-
Independent time delay for
residual current at 0 to 2 x I
set
(0.000 - 60.000) s
±0.2% or ±25 ms
whichever is
greater
Independent time delay for
residual voltage at 0.8 to 1.2 x
U
set
(0.000 - 60.000) s
±0.2% or ±25 ms
whichever is
greater
Independent dropoff-delay for
residual voltage at 1.2 to 0.8 x
U
set
(0.000 - 60.000) s
±0.2% or ±25 ms
whichever is
greater
Operating mode
No Filter, NoPref
Cyclic: 1231c, 1321c
Acyclic: 123a, 132a, 213a, 231a, 312a,
321a
1MRK 506 382-UEN A
Section 6
Impedance protection
Line distance protection REL650 2.2 IEC
157
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...