background image

Hazardous voltage.
Will cause death or
serious injury.

Turn OFF and lock out all
power supplying this
device before installing
or servicing accessory.

Siemens Energy & Automation, Inc.
Bellefontaine, Ohio 43311 U.S.A.

Installation Instructions

Item: Instructions for Installation of Circuit Breaker
Plug-In Adapters.  Cat. No.’s TCF2
(2-Pole) and TCF3 (3-Pole).
For use with: SIEMENS

® 

FD Frame Circuit Break-

ers and Molded Case Switches in conjunction with
plug-in-tulip connector assemblies. Cat. No.’s
PC4753, PC4754 and PM4754

Page of 3

Pc. No. 410902A01

BREAKERS  TYPES

FJ6(ETI), F6, HF6, FM6, FMK, CLF(ETI), HFJ6,
(H)(H)FXD6(ETI), FD6, (H)(H)FD6, CFD6(ETI), FFC, FFF

SAFETY INSTRUCTIONS

Fig. 4

Install As Shown

NOTE: This instruction outlines the recommended
installation procedure.

1. Circuit Breaker Preparation

The circuit breaker should be in the OFF/”O”
position before installing the plug-in-tulip adapter
kit.  Turn off and lock out all power supplying
this device before installing.  Verify that 

NO volt-

age is present before proceeding with task.

Remove Pressure Wire Connectors From
Breaker If Present

2. Place tulip clip assembly (6) on back of breaker

in recess provided in base molding.  Secure in
place with 5/16 flatwashers (7), lockwashers (8)
and 5/16 - 18 X 1 1/2 round head screws (9)
furnished.  (Exception - on CLF and CFD break-
ers use 2” long screws on load side.)  Torque
screws to 5-6 lb-Ft. [6.78-8.13 N/m] to assure a
good electrical connection.  Repeat this proce-
dure for the remaining tulip clip assemblies.

3. Slide upper end shields (10) and insert lower

end shields (11) with beveled end facing breaker
and press into slots provided at line and load
end of breaker.

4. Add accessory label (12) to top of breaker as

indicated in Fig. 4.