RFPEZx
X1Zx+XNZx
X1Zx+XNZx
RFPEZx
R1Zx+RNZx
RFPEZx
RFPEZx
RFPEZx
RFPEZx
R
R1Zx+RNZx
(Ohm/loop)
IEC11000415-2-en.vsdx
X0Zx-X1Zx
XNZx
3
=
R0Zx-R1Zx
RNZx
3
=
X (Ohm/loop)
N
φ
N
φ
IEC11000415 V2 EN-US
Figure 33:
ZMFPDIS Characteristic for phase-to-earth measuring, ohm/loop
domain
The faulty loop in relation to the fault type can be presented as in figure
main intention with this illustration is to make clear how the fault resistive reach
should be interpreted and set. Note in particular that the setting RFPPZx always
represents the total fault resistance of the loop, regardless the fact that the fault
resistance (arc) may be divided into parts like for three-phase or phase-to-phase
faults. The R1Zx + jX1Zx represent the positive sequence impedance from the
measuring point to the fault location.
1MRK 506 382-UEN A
Section 6
Impedance protection
Line distance protection REL650 2.2 IEC
99
Technical manual