Name
Values (Range)
Unit
Step
Default
Description
UnderTrigLe03
0 - 200
%
1
50
Under trigger level for analog channel 3
in % of signal
OverTrigOp03
Off
On
-
-
Off
Use over level trigger for analog channel
3 (on) or not (off)
OverTrigLe03
0 - 5000
%
1
200
Overtrigger level for analog channel 3 in
% of signal
NomValue04
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 4
UnderTrigOp04
Off
On
-
-
Off
Use under level trigger for analog
channel 4 (on) or not (off)
UnderTrigLe04
0 - 200
%
1
50
Under trigger level for analog channel 4
in % of signal
OverTrigOp04
Off
On
-
-
Off
Use over level trigger for analog channel
4 (on) or not (off)
OverTrigLe04
0 - 5000
%
1
200
Over trigger level for analog channel 4 in
% of signal
NomValue05
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 5
UnderTrigOp05
Off
On
-
-
Off
Use under level trigger for analog
channel 5 (on) or not (off)
UnderTrigLe05
0 - 200
%
1
50
Under trigger level for analog channel 5
in % of signal
OverTrigOp05
Off
On
-
-
Off
Use over level trigger for analog channel
5 (on) or not (off)
OverTrigLe05
0 - 5000
%
1
200
Over trigger level for analog channel 5 in
% of signal
NomValue06
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 6
UnderTrigOp06
Off
On
-
-
Off
Use under level trigger for analog
channel 6 (on) or not (off)
UnderTrigLe06
0 - 200
%
1
50
Under trigger level for analog channel 6
in % of signal
OverTrigOp06
Off
On
-
-
Off
Use over level trigger for analog channel
6 (on) or not (off)
OverTrigLe06
0 - 5000
%
1
200
Over trigger level for analog channel 6 in
% of signal
NomValue07
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 7
UnderTrigOp07
Off
On
-
-
Off
Use under level trigger for analog
channel 7 (on) or not (off)
UnderTrigLe07
0 - 200
%
1
50
Under trigger level for analog channel 7
in % of signal
OverTrigOp07
Off
On
-
-
Off
Use over level trigger for analog channel
7 (on) or not (off)
OverTrigLe07
0 - 5000
%
1
200
Over trigger level for analog channel 7 in
% of signal
NomValue08
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 8
UnderTrigOp08
Off
On
-
-
Off
Use under level trigger for analog
channel 8 (on) or not (off)
UnderTrigLe08
0 - 200
%
1
50
Under trigger level for analog channel 8
in % of signal
Table continues on next page
1MRK 506 382-UEN A
Section 14
Monitoring
Line distance protection REL650 2.2 IEC
597
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...