IEC10000029-1-en.vsd
A3RADR
A2RADR
A1RADR
SMAI
AI1
AI2
AI3
AI4
AI3P
^GRP2L1
^GRP2L2
^GRP2L3
Block
^GRP2N
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
...
A4RADR
INPUT31
INPUT32
INPUT33
INPUT34
INPUT35
INPUT36
...
INPUT40
Internal analogue signals
External
analogue
signals
AIN
Type
IEC10000029 V1 EN-US
Figure 312:
Analog input function blocks
The external input signals will be acquired, filtered and skewed and (after
configuration) available as an input signal on the AxRADR function block via the
SMAI function block. The information is saved at the Disturbance report base
sampling rate (1000 or 1200 Hz). Internally calculated signals are updated
according to the cycle time of the specific function. If a function is running at
lower speed than the base sampling rate, Disturbance recorder will use the latest
updated sample until a new updated sample is available.
If the IED is preconfigured the only tool needed for analog configuration of the
Disturbance report is the Signal Matrix Tool (SMT, external signal configuration).
In case of modification of a preconfigured IED or general internal configuration the
Application Configuration tool within PCM600 is used.
The preprocessor function block (SMAI) calculates the residual quantities in cases
where only the three phases are connected (AI4-input not used). SMAI makes the
information available as a group signal output, phase outputs and calculated
residual output (AIN-output). In situations where AI4-input is used as an input
signal the corresponding information is available on the non-calculated output
(AI4) on the SMAI function block. Connect the signals to the AxRADR
accordingly.
For each of the analog signals,
Operation
=
On
means that it is recorded by the
disturbance recorder. The trigger is independent of the setting of
Operation
, and
triggers even if operation is set to
Off
. Both undervoltage and overvoltage can be
used as trigger conditions. The same applies for the current signals.
1MRK 506 382-UEN A
Section 14
Monitoring
Line distance protection REL650 2.2 IEC
615
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...