Section 8
Voltage protection
8.1
Two step undervoltage protection UV2PTUV
IP14544-1 v3
8.1.1
Identification
M16876-1 v7
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Two step undervoltage protection
UV2PTUV
3U<
SYMBOL-R-2U-GREATER-THAN
V2 EN-US
27
8.1.2
Functionality
M13789-3 v12
Undervoltages can occur in the power system during faults or abnormal conditions.
The two-step undervoltage protection function (UV2PTUV) can be used to open
circuit breakers to prepare for system restoration at power outages or as a long-time
delayed back-up to the primary protection.
UV2PTUV has two voltage steps, each with inverse or definite time delay.
It has a high reset ratio to allow settings close to the system service voltage.