PID-3923-SETTINGS v7
Table 10:
TRM_7I_5U Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
CTStarPoint1
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec1
1 - 10
A
1
1
Rated CT secondary current
CTprim1
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint2
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec2
1 - 10
A
1
1
Rated CT secondary current
CTprim2
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint3
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec3
1 - 10
A
1
1
Rated CT secondary current
CTprim3
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint4
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec4
1 - 10
A
1
1
Rated CT secondary current
CTprim4
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint5
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec5
1 - 10
A
1
1
Rated CT secondary current
CTprim5
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint6
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec6
1 - 10
A
1
1
Rated CT secondary current
CTprim6
1 - 99999
A
1
3000
Rated CT primary current
CTStarPoint7
FromObject
ToObject
-
-
ToObject
ToObject= towards protected object,
FromObject= the opposite
CTsec7
1 - 10
A
1
1
Rated CT secondary current
CTprim7
1 - 99999
A
1
3000
Rated CT primary current
VTsec8
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim8
0.05 - 2000.00
kV
0.05
400.00
Rated VT primary voltage
VTsec9
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim9
0.05 - 2000.00
kV
0.05
400.00
Rated VT primary voltage
VTsec10
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim10
0.05 - 2000.00
kV
0.05
400.00
Rated VT primary voltage
VTsec11
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim11
0.05 - 2000.00
kV
0.05
400.00
Rated VT primary voltage
VTsec12
0.001 - 999.999
V
0.001
110.000
Rated VT secondary voltage
VTprim12
0.05 - 2000.00
kV
0.05
400.00
Rated VT primary voltage
1MRK 506 382-UEN A
Section 3
Analog inputs
Line distance protection REL650 2.2 IEC
55
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...