PID-3581-OUTPUTSIGNALS v6
Table 265:
ECPSCH Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip signal by communication scheme logic
CS
BOOLEAN
Carrier Send by Communication Scheme Logic
CRL
BOOLEAN
Carrier Receive from Communication Scheme
Logic
LCG
BOOLEAN
loss of carrier guard signal
12.4.5
Settings
PID-3581-SETTINGS v6
Table 266:
ECPSCH Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
SchemeType
Off
Intertrip
Permissive UR
Permissive OR
Blocking
-
-
Permissive UR
Scheme type, Mode of Operation
tCoord
0.000 - 60.000
s
0.001
0.035
Communication scheme coordination
time
tSendMin
0.000 - 60.000
s
0.001
0.100
Minimum duration of a carrier send
signal
Table 267:
ECPSCH Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Unblock
Off
NoRestart
Restart
-
-
Off
Operation mode of unblocking logic
tSecurity
0.000 - 60.000
s
0.001
0.035
Security timer for loss of carrier guard
detection
12.4.6
Operation principle
M13922-4 v5
The four step directional residual overcurrent protection EF4PTOC is configured to
give input information, that is directional fault detection signals, to the ECPSCH
logic:
1MRK 506 382-UEN A
Section 12
Scheme communication
Line distance protection REL650 2.2 IEC
451
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...