and the behavior of each component are compared between the trigger and the post
processing time. If there are any differences, then it will be added in the header file
under section
Changed_settings
.
In the HDR file, section tag
Settings
has an attribute tag called
function
which
includes parameters that are grouped based on the function instance. The function
tag has content called
name
which is the function name provided together with the
user-defined name in brackets similar to the HMI.
Status
content will indicate the
runtime status of the function and
beh
content will indicate the IEC61850 behavior
of the components, if supported. Non runtime components will not have
status
and
beh
tag contents.
Parameters of the function are listed as a child tag
Set
with contents
name
,
value
and
unit
:
•
name
— parameter name same as HMI
•
value
— actual parameter value
•
unit
— parameter unit
The
changed_settings
attribute tag is similar to the
settings
section. It contains
functions which have changes in parameter value or runtime status or IEC61850
behavior when compared with trigger and post-processing settings values.
Fault locator (FL)
M12155-186 v4
The fault location function calculates the distance to fault.
Time tagging
M12155-194 v1
The IED has a built-in real-time calendar and clock. This function is used for all
time tagging within the disturbance report
Recording times
M12155-99 v5
Disturbance report DRPRDRE records information about a disturbance during a
settable time frame. The recording times are valid for the whole disturbance report.
Disturbance recorder (DR), event recorder (ER) and indication function register
disturbance data and events during tRecording, the total recording time.
The total recording time, tRecording, of a recorded disturbance is:
tRecording =
PreFau PostFaultrecT or PreFau TimeLimit, depending on
which criterion stops the current disturbance recording
1MRK 506 382-UEN A
Section 14
Monitoring
Line distance protection REL650 2.2 IEC
613
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...