IEC05000748_2_en.vsd
UN
ST1
TR1
ST2
TR2
START
TRIP
Comparator
UN > U1>
Start
t2
tReset2
&
Trip
Output
Logic
Step 2
Phase 1
Phase 1
Time integrator
tIReset2
ResetTypeCrv2
START
Start
t1
tReset1
&
Trip
Output
Logic
Step 1
Time integrator
tIReset1
ResetTypeCrv1
Comparator
UN > U2>
START
TRIP
TRIP
OR
OR
IEC05000748 V2 EN-US
Figure 149:
Schematic design of Two step residual overvoltage protection
ROV2PTOV
8.3.8
Technical data
M13317-2 v14
Table 160:
ROV2PTOV technical data
Function
Range or value
Accuracy
Operate voltage, step 1 - step 2
(1.0-200.0)% of
UBase
± 0.5% of U
r
at U ≤
U
r
± 0.5% of U at U > U
r
Absolute hysteresis
(0.0–50.0)% of
UBase
± 0.5% of U
r
at U ≤
U
r
± 0.5% of U at U > U
r
Inverse time characteristics for low and
-
See table
Definite time delay low step (step 1) at 0
to 1.2 x U
set
(0.00–6000.00) s
± 0.2% or ± 45 ms
whichever is greater
Definite time delay high step (step 2) at 0
to 1.2 x U
set
(0.000–60.000) s
± 0.2% or ± 45 ms
whichever is greater
Table continues on next page
Section 8
1MRK 506 382-UEN A
Voltage protection
296
Line distance protection REL650 2.2 IEC
Technical manual
Содержание RELION 650 SERIES
Страница 1: ...RELION 650 SERIES Line distance protection REL650 Version 2 2 Technical manual ...
Страница 2: ......
Страница 46: ...40 ...
Страница 56: ...50 ...
Страница 164: ...158 ...
Страница 264: ...258 ...
Страница 304: ...298 ...
Страница 320: ...314 ...
Страница 338: ...332 ...
Страница 438: ...432 ...
Страница 468: ...462 ...
Страница 534: ...528 ...
Страница 646: ...640 ...
Страница 660: ...654 ...
Страница 676: ...670 ...
Страница 800: ...794 ...
Страница 836: ...830 ...
Страница 890: ...884 ...
Страница 894: ...888 ...
Страница 940: ...934 ...
Страница 941: ...935 ...