- 99 -
000566AG
5 - Installation
C
onfigurable Relay connection (ALARM)
The inverter is equipped with a multifunction
relay with configurable
activation. It can be connected with normally open contact (being
connected between the NO terminal and the common contact C) and
with normally closed contact (being connected between the NC terminal
and the common contact C).
Different types of devices (light, sound, etc.) can be connected to the
relay, provided they comply with the following requirements:
Alternating current
Maximum Voltage: 240 Vac
Maximum Current: 1 A
Direct current
Maximum Voltage: 30 Vdc
Maximum Current: 0.8 A
Cable requirements
External diameter: from 5 to 17 mm
Conductor cross-section: from 0.14 to 1.5 mm
2
This contact can be used in different operating configurations that can
be selected by accessing the "Inverter → Settings → Alarms" menu. The
selectable modes are described in the paragraph about the "Inverter
Menu → Settings".
22
Impostazioni
Allarme
ENTER
Inverter
ENTER
Password 0000
ENTER