- 60 -
000561AG
5 - Installation
• Avoid
electromagnetic interference that can compromise the correct
operation of electronic equipment, with the consequent hazards
• The ambient temperature of the installation location must be between
5°C and 35°C to guarantee the optimal operation of the battery unit
(REACT-BATT-AP1). Here below are the functions available from the
system on the basis of the ambient temperature:
T1 - Optimal operation of the REACT system
T2 - Correct operation of the REACT system with possible reduction in
the lifetime of the batteries
T3 - Partial operation of the battery which limits its functioning to
discharge only
T4 - Operation limited to the inverter part only. Management of the
battery is disabled.
-20
-10
0
+5
+35 +40 +45
+55
T1
T2
T3
T4
°C
T2 T3
T4
• Consult the technical data to check the required
environmental
conditions (protection rating, temperature, humidity, altitude, etc.)
Final installation of the REACT system must not compromise access to any externally located
disconnection devices.
Please refer to the warranty terms and conditions to evaluate any possible warranty exclusions
due to improper installation.