- 160 -
000570BG
8 - Maintenance
- Error code
- Error message
- Warning
Name of Alarm and Cause
Solution
E058
- Pin vs Pout check
error
-
Yellow LED
Error in the check of Pin vs Pout:
The error occurs if the difference between the
measured value of input power and that of output
power is greater than the limit imposed internally to
the inverter.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E065
- Stop Button
-
Yellow LED
Emergency (stop) button activated:
This code marks the activation of the emergency
button (button pressed). This warning is activated only
where there is DC or AC voltage as, if the emergency
button is pressed while it is operating only by battery,
it causes the whole system to shut down.
• Check that the emergency button has been pressed and if
necessary deactivate it.
- If the warning persists even though the button has been
deactivated, contact customer assistance.
E066
- Charger-Bulk
-
Yellow LED
Error in the “Charger” circuit:
Error internal to inverter relating to the bulk voltage of
the circuit linked to battery charger
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E067
- Charger - OV
-
Yellow LED
Overvoltage of "battery charger"
("Charger" circuit):
Error inside the inverter. The alarm is raised when
the battery charger voltage exceeds the overvoltage
threshold (internal unchangeable threshold).
•
The error might continue when the battery is disconnected
(e.g. activation of emergency button).
• If the message persists and is not linked to the battery being
disconnected, contact customer assistance.
E068
- Charger - OC
-
Yellow LED
Overcurrent of "battery charger"
("Charger" circuit):
Error inside the inverter.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E069
- Charger-SlowRamp
-
Yellow LED
Error internal to inverter linked to the battery pack
charger circuit ("Charger" circuit"):
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E070
- Charger-preChar.
-
Yellow LED
Error inside the inverter.
• Error inside the inverter probably linked to the fuse in the
damaged battery pack; the error cannot be verified externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E074
- Internal error
-
Yellow LED
Communication error inside the inverter:
The alarm occurs when there are communication
problems between the control devices inside the
inverter.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E077
- Internal Error
-
Yellow LED
Error in the system configuration:
Error inside the inverter
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E078
- Riso Test fail
-
Yellow LED
Riso test error:
Problem detected during the Riso test phase.
• Error inside the inverter and cannot be checked externally.
- If the problem persists (once the inverter has been switched
off and back on again), contact customer assistance.
E079
- Wrong Sequence
-
Yellow LED
Incorrect Phases connection
(Only triphase models) The phases have not been
connected correctly to the AC output
• Invert two of the phases of the grid wiring to the AC terminal
block of the inverter.