ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 218
7.5.1.9.1.2.5.7.4
—
Dependent Parameter
Input for temperature limit sensor
Options:
Via group object
Via physical device input a
Via physical device input b
Via physical device input c
Via physical device input d
•
Via group object
: The temperature value is received via a dedicated group object. The depen-
dent
Additional-stage cooling limit temperature
group object is enabled.
•
Via physical device input x
: The temperature value is acquired via a temperature sensor con-
nected (to the selected input).
Note
A temperature sensor must be actually connected to the temperature input selected and the input
for the sensor must have been correctly parameterized, otherwise the limit temperature function
does not work.
If one of the device inputs is selected here as the input for the limit temperature, this input is no
longer used to acquire the room temperature. It is therefore not possible to use the same temper-
ature sensor for the measurement of the room temperature and for the measurement of the limit
temperature.