![ABB i-bus FCC/S 1 1 Series Скачать руководство пользователя страница 148](http://html.mh-extra.com/html/abb/i-bus-fcc-s-1-1-series/i-bus-fcc-s-1-1-series_product-manual_3070148.webp)
ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 148
7.4.2.1.1.10
Fan output after ETS download
This parameter is only visible for:
•
FCC/S 1.3.1.1
•
FCC/S 1.3.2.1
•
FCC/S 1.5.1.1
•
FCC/S 1.5.2.1
Options:
Unchanged
Applies control value
33 %
66 %
100 %
This parameter is used to specify the fan speed that is to apply after a download.
•
Unchanged
: The same fan speed as before the download. The status of the automatic mode
also remains unchanged. The fan follows the valve control value if the automatic mode is ac-
tive.
•
Applies control value
: The speed is dependent on the valve control value, the automatic mode
is active. If the automatic mode was deactivated before the download, it is activated.
•
33 %
: The fan runs with speed 33 % in the manual mode.
•
66 %
: The fan runs with speed 66 % in the manual mode.
•
100 %
: The fan runs with speed 100 % in the manual mode.
7.4.2.1.1.11
Relay output after ETS download
This parameter does not apply to FCC/S 1.4.1.1.
Options:
Unchanged
On
Off
The reaction of the relay output after the download is specified using this parameter.
•
Unchanged
: The relay remains in its actual position after the download.
•
On
: The relay is switched on after the download.
•
Off
: The relay is switched off after the download.