ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 294
7.12.1.1.2
—
Dependent Parameter
Max. manual reduction in heating mode via KNX
This parameter is only displayed if you select
No
when setting
Connect analog room control unit to
physical device input a
.
Options:
0…3…9
The parameter determines the maximum setpoint reduction that can be manually set via KNX in
Heating mode. Use the
Request setpoint adjustment
group object to reduce the Comfort heating
setpoint by a maximum of the value set here.
Note
If the object receives a value below this, the maximum possible reduction is applied, and a re-
quest with the new temperature is confirmed on the
Confirm setpoint adjustment
group object.
7.12.1.1.3
—
Dependent Parameter
Max. manual increase in cooling mode via KNX
This parameter is only displayed if you select
No
when setting
Connect analog room control unit to
physical device input a
.
Options:
0…3…9
The parameter determines the maximum setpoint increase that can be manually set via KNX in
Cooling mode. Use the
Request setpoint adjustment
group object to increase the Comfort cooling
setpoint by a maximum of the value set here.
Note
If the object receives a value that exceeds this, the maximum possible increase is applied, and a
request with the new temperature is sent via KNX on the
Confirm setpoint adjustment
group ob-
ject.
7.12.1.1.4
—
Dependent Parameter
Max. manual reduction in cooling mode via KNX
This parameter is only displayed if you select
No
when setting
Connect analog room control unit to
physical device input a
.
Options:
0…3…9
The parameter determines the maximum setpoint reduction that can be manually set via KNX in
cooling mode. You can use the
Request setpoint adjustment
group object to reduce the Comfort
cooling setpoint by a maximum of the value set here.
Note
If the object receives a value below this, the maximum possible reduction is applied, and a re-
quest with the new temperature is confirmed on the
Confirm setpoint adjustment
group object.