ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 297
7.12.1.1.8
—
Dependent Parameter
Reset manual adjustment via KNX when operating mode changes
This parameter is only displayed if you select
No
when setting
Connect analog room control unit to
physical device input a
.
Options:
No
Yes
•
No
: When the device changes operating modes, the manual adjustment is cleared from active
parameters and replaced with the parametrized target temperature for the new mode plus any
change sent via the Base setpoint group object.
Example:
Comfort temperature 21 °C + manual adjustment 1.5 °C = 22.5 °C. Change to Eco mode with a
parametrized temperature of 17 °C. The device adjusts the temperature to 17 °C because the
manual adjustment has been cleared.
•
Yes
: This option factors in the manual setpoint adjustment on top of the new operating mode
temperature.
Example:
Comfort temperature 21 °C + manual adjustment 1.5 °C = 22.5 °C. Change to Eco mode with a
parametrized temperature of 17 °C. The device adjusts the temperature to 18.5 °C because the
manual adjustment has been factored in.
7.12.1.1.9
—
Dependent Parameter
Reset manual adjustment via KNX using group object
This parameter is only displayed if you select
No
when setting
Connect analog room control unit to
physical device input a
.
Options:
No
Yes
When this option is activated, the manual adjustment can be cleared at any time via the
Reset
manual setpoint adjustment
group object.
Selecting
No
hides this group object and you can no longer use it to reset manual setpoint adjust-
ment.
Example:
Resetting manual adjustment of all the devices in a building using a time scheduler in the system.
7.12.1.1.10
—
Dependent Parameter
Slave display indicates
This parameter is only displayed if you select
No
when setting
Connect analog room control unit to
physical device input a
.
Options:
Absolute
Relative
This parameter determines whether a slave displays a setpoint as absolute or relative.