ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 274
7.10.1.3.5
—
Dependent Parameter
Minimum dwell period in fan speed
Options:
0…5…600
This parameter defines the dwell time for a fan speed until it switches to the next higher or lower
fan speed. The entry is made in seconds.
A setting of 0 means instant switching. The minimum relay switching times can be found in the
technical data.
The dwell time is only taken into account in automatic operation.
7.10.1.3.6
—
Dependent Parameter
Return from manual fan adjustment to automatic mode
Options:
Via group object
Automatic (time)
Via group object or automatic (time)
This parameter is used to define how a return from manual fan adjustment to the automatic mode
is to occur.
•
Via group object
: The return to the automatic mode is only via the
Activate/deactivate fan
automation
group object.
•
Automatic (time)
: The return is automatic after an adjustable time. The dependent parameter
Reset time
appears.
•
Via group object or automatic (time)
: The reset is both via the
Activate/deactivate fan
automation
group object and after an adjustable time. The dependent parameter
Reset time
ap-
pears.
7.10.1.3.6.1
—
Dependent Parameter
Reset time
Options:
00:00:30…01:00:00…18:12:15
After the time specified here has elapsed, the fan returns to automatic operation.
The time starts again after each manual adjustment of the fan.