![ABB i-bus FCC/S 1 1 Series Скачать руководство пользователя страница 147](http://html.mh-extra.com/html/abb/i-bus-fcc-s-1-1-series/i-bus-fcc-s-1-1-series_product-manual_3070147.webp)
ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 147
7.4.2.1.1.7
Heating/cooling mode after ETS download/reset
Options:
Heating
Cooling
7.4.2.1.1.8
Control value after ETS download
Options:
Unchanged
Select
This parameter specifies which control value is to apply after a download until the controller has
calculated a new control value.
The value specified here applies until a new control value has been received via the bus.
•
Unchanged:
The same control value as before the download applies.
•
Select
: A control value can be specified. This control value then applies until a new control
value is calculated/a new control value is received via the bus. The
Control value
dependent
parameter is displayed.
7.4.2.1.1.8.1
—
Dependent Parameter
Control value
Options:
0…100
This parameter is used to specify the control value that is to apply after bus voltage recovery until a
new control value is received.
7.4.2.1.1.9
Fan output after ETS download
This parameter is only visible for:
•
FCC/S 1.1.1.1
•
FCC/S 1.1.2.1
•
FCC/S 1.2.1.1
•
FCC/S 1.2.2.1
•
FCC/S 1.4.1.1
Options:
Unchanged
Applies control value
1
2
3
This parameter is used to specify the fan speed that is to apply after a download.
•
Unchanged
: The same fan speed as before the download. The status of the automatic mode
also remains unchanged. The fan follows the valve control value if the automatic mode is ac-
tive.
•
Applies control value
: The speed is dependent on the valve control value, the automatic mode
is active. If the automatic mode was deactivated before the download, it is activated.
•
1
: The fan runs with speed 1 in the manual mode.
•
2
: The fan runs with speed 2 in the manual mode.
•
3
: The fan runs with speed 3 in the manual mode.