ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 287
7.10.2.8
Send status values
Options:
On change
Cyclically
On change and cyclically
On request
After a change or request
On request and cyclically
After a change or request and cyclically
This parameter defines when the fan output status values are to be sent. This parameter affects
the following fan output group objects:
•
Status Fan On/Off
•
Status Fan Speed
•
Status Fan Speed 1
•
Status Fan Speed 2
•
Status Fan Speed 3
•
Status Fan Automatic
If the parameter
Switch fan speed via 1-bit objects
is parameterized with the
Deactivated
option,
the group objects
Status Fan Speed 1
,
Status Fan Speed 2
and
Status Fan Speed 3
are not dis-
played.
•
On change
: The values are sent on a change in the object values (e.g. change from 0 to 1).
With the
Status Control value
group object, the values are sent if the change in the control
value is at least 1 %.
•
Cyclically
: If this option is selected, the status values are sent automatically after an adjustable
time has elapsed. The
Every
dependent parameter is displayed.
•
On change and cyclically
: The values are sent on a change and cyclically.
•
On request
: All status values are sent on the receipt of a command via the
Request status
values
group object.
•
After a change or request
: The values are sent on request and on a change.
•
On request and cyclically
: The values are sent on a change and cyclically.
•
After a change or request and cyclically
: The values are sent on request and on a change and
cyclically. The
Every
dependent parameter is displayed.
7.10.2.8.1
—
Dependent Parameter
Every
Options:
00:00:30…00:05:00…18:12:15
This parameter is used to set the time after which the status values are to be sent cyclically. The
group objects are sent after each cycle.