FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 215
7.5.1.9.1.2.5.4
—
Dependent Parameter
Cooling PWM cycle
This parameter is only visible on the selection of the
PI PWM (On/Off)
option.
Options:
0…15…60
Using the value set here, the cycle time for the control value for the PWM signal calculated from
the PI controller's control value is specified. Depending on the control value, the selected cycle
time is divided into an On and Off signal.
Therefore, a control value output of 33 % with a PWM cycle of 15 min signifies an On phase of five
minutes and an Off phase of 10 min.
Note
The value is only sent if the control value changes (from 0 to 1 or vice versa).
At the start of a cycle a 1 is output and, corresponding to the control value, a 0 after the time x.
If the control value is 0 %, on reaching this control value a 0 is output once. The next value is
only sent if the control value changes.
Example:
Cooling PWM cycle: 15 min
Control value: 33 %
Times
Sent value
0 min
1
5 min
0
15 min
1
20 min
0
30 min
1
…
…
New control value: 0 %
Times
Sent value
60 min
0
75 min
–
90 min
–
…
…
New control value: 66 %
Times
Sent value
120 min
1
130 min
0
135 min
1
145 min
0
…
…