ABB i-bus
®
KNX
Group objects
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 348
No.
Function
Group object name Data Type
Flag
99
Confirm setpoint adjustment
(master)
Channel – Controller 2 bytes / 2 bytes / 1
byte
DPT 9.001 / 9.002 /
6.010
C, R, T
This group object is enabled if the parameter
Connection of an analog room control unit to physical device
input a
in the
Setpoint adjustment
parameter window is set to
No
.
This group object is hidden in actuator mode.
The group object transmits a setpoint change between the controller (master) and the slave or any other de-
vice. This group object confirms a setpoint adjustment requested via the group object
Request setpoint
adjustment
so that the new value becomes known to the requesting device as well.
Refer to group object 95 for the various data point types. The data point type of this group object depends on
the same settings.
Note
If a slave is used:
This group object must be connected to the corresponding group object of the slave for master/slave
operation to function.
100
Request heating/cooling (mas-
ter)
Channel – Controller 1 bit
DPT 1.100
C, W
This group object is visible in controller mode only if the parameter
Heating/Cooling changeover
is set to
Via
slave and via group object
in the
Application parameters
parameter window.
This group object is hidden in actuator mode.
This group object synchronizes between the controller (master) and the slave. This group object must be
connected to the slave's group object of the same name for this purpose.
The group object synchronizes the heating/cooling status between the controller (master) and the slave.
101
Request fan manually (slave)
Channel – Actuator
1 bit
DPT 1.001
C, W
This group object is enabled if, in actuator mode, the parameter
Connection of an analog room control unit to
physical device input a
in the
Setpoint adjustment
parameter window is set to
Yes
.
This group object is hidden in controller mode.
When an analog room control unit is connected, this group object establishes communication between the
actuator and the controller. The analog room control unit can adjust the fan automation in this mode. The ad-
justment is then transmitted to the controller via this group object.
This group object requests changing out of/into fan automation.
The group object must be connected to the controller's (master's) group object of the same name for this pur-
pose.