ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 126
7.4.1.2.1.1.5
—
Dependent Parameter
Use 6-way valve
This parameter is only visible for:
•
FCC/S 1.2.1.1
•
FCC/S 1.2.2.1
•
FCC/S 1.3.1.1
•
FCC/S 1.3.2.1
This parameter is not visible if the
Basic-stage heating
or
Basic-stage cooling
parameters are de-
activated. This parameter is also only visible if the
4-pipe
option has been selected in the
Type of
heating/cooling system
parameter.
Options:
No
Yes
This parameter is used to parameterize the usage of a 6-way valve on the device. The 6-way valve
is used to control both the heating and cooling stages at the same time. For this purpose the drive
in the 6-way valve is connected to valve output A and the control values for heating and cooling
are output on this output.
Note
The usage of a 6-way valve is only possible for the two basic stages.
If one of the basic stages has been deactivated or the basic-stage heating is used for a non-wa-
ter type of heating (e.g. electric heater), it is not possible to use a 6-way valve.
If
Yes
has been selected, the dependent parameter
Valve type
in the
Valve output A
parameter
window is pre-configured to
6-way valve
. The
Actuate basic-stage heating via
and
Actuate basic-
stage cooling via
parameters are set to
Output A
.
Note
To prevent an erroneous configuration, none of the dependent parameters can be changed as
long as the usage of a 6-way valve is parameterized.