Manual Energy Storage Inverter ESI-S
The ESI-Manager user interface 133
For setting up the system clock, go to [/Welcome/Settings/Installation set./Clock]
In multi-master units these functions need to be set up in each master-unit in order to
obtain full redundancy.
The ESI is equipped with a system clock, which can be modified by the user. The date
and the time (Hr, Min. Sec) can be changed. The hour is presented in 24-hour format and
is set up for the time zone GMT +1.
7.9.4.4 Setting Password
For setting up the password, go to [/Welcome/Settings/Installation set./Password]
A password setting allows the user to set a software lock of the settings. Once set and
the installation are locked, the crucial parameters cannot be changed unless the
software lock is removed.
A customer can choose a 4 digit password of his choice to activate the software lock.
During selection, first the old password (default: 1234) needs to be entered followed by
a new password. The new password needs to be confirmed. Now pressing the
button saves the new password.
7.9.4.5 Installation Locking