Program features 155
Protection functions
The following functions can be used to check and ensure proper operation of elevator
control in different operating conditions: Speed match, Inverter overload, Motor stall
and Leveling overtime stop.
Other protection functions cover Thermal motor protection, DC voltage control and
Programmable protection functions.
Speed match
The Speed match function checks that the motor actual speed (speed estimate or
measured with an encoder, see parameter
SPEED FB SEL) follows the speed
reference within the desired window during acceleration, deceleration and when
running in a steady state (at set-point speed). The function also ensures that the
brake does not slip while the drive is in a stopped state with the brake closed.
You can enable the Speed match function with parameter
SPEED MATCH.
There are two parameters for defining the speed match deviation:
SPD STD
DEV LVL is used for checking the deviation in a steady state, whereas
SPD
RMP DEV LVL is used for checking the deviation during acceleration and
deceleration.
While the drive is running, it trips on fault SPEED MATCH if the following conditions
are met.
• The motor is running in a steady state and the difference of the motor actual
speed and the ramped speed reference is greater than the value of parameter
SPD STD DEV LVL for a period longer than defined with parameter
SPEED MATCH DLY.
Example: If parameter
SPD STD DEV LVL is set to 0.5 m/s, the drive will
not trip on fault SPEED MATCH as long the difference of the motor actual speed
and the speed reference does not exceed 0.5 m/s (that is, it does not go outside
the enclosed area in the figure below) for a period longer than defined with
parameter
• The motor is accelerating/decelerating and the difference of the motor actual
speed and the ramped speed reference is greater than the value of parameter
SPD RMP DEV LVL for a period longer than defined with parameter
SPEED MATCH DLY.
Example: If parameter
SPD RMP DEV LVL is set to 0.6 m/s, the drive will
not trip on fault SPEED MATCH during acceleration/deceleration as long as the
difference of the motor actual speed and the ramped speed reference does not
exceed 0.6 m/s (that is, it does not go outside the enclosed area in the figure
below) for a period longer than defined with parameter
SPEED MATCH
DLY (0.5 s).
Содержание ACL30
Страница 1: ...ABB high performance elevator drives User s manual ACL30 elevator drive ...
Страница 4: ......
Страница 20: ...20 Safety instructions ...
Страница 34: ...34 Operation principle and hardware description ...
Страница 42: ...42 Planning the cabinet installation ...
Страница 60: ...60 Planning the electrical installation ...
Страница 126: ...126 Using the control panel ...
Страница 318: ...318 Maintenance ...
Страница 334: ...334 The Safe torque off function ...
Страница 338: ...338 Mains chokes ...
Страница 342: ...342 EMC filters ...
Страница 348: ...Dimension drawings 348 Frame size B D1 D2 W H1 H2 ...
Страница 349: ...Dimension drawings 349 ...
Страница 350: ...Dimension drawings 350 Frame size C D1 D2 H2 H1 W ...
Страница 351: ...Dimension drawings 351 ...
Страница 352: ...Dimension drawings 352 Frame size D ...
Страница 354: ...354 Dimension drawings EMC filters JFI 0x ...
Страница 356: ...356 Dimension drawings Brake resistors JBR xx ...
Страница 358: ...358 Dimension drawings ...
Страница 360: ...Contact us www abb com drives www abb com drivespartners 3AXD50000036355 Rev B EN EFFECTIVE 2016 11 21 ...