160 Program features
WARNING!
The connection of motor temperature sensor requires double or
reinforced insulation between motor live parts and the sensor because the
thermistor input on the JCU control unit is not insulated according to
IEC 60664.
If the assembly does not fulfill the requirement,
- protect the I/O board terminals against contact and make sure that it is not
connected to any other equipments
or
- isolate the temperature sensor from the I/O terminals.
The figure below shows a motor temperature measurement when thermistor input TH
is used.
For encoder interface module FEN-xx connection, see the
User’s manual
of the
appropriate encoder interface module.
Settings
Parameters
Additional information
Settings for thermal protection of the motor.
Motor
T
JCU Control Unit
TH
AGND
10 nF
One PTC or KTY84 sensor
Motor
T
JCU Control Unit
TH
AGND
T
T
Three PTC sensors
10 nF
Содержание ACL30
Страница 1: ...ABB high performance elevator drives User s manual ACL30 elevator drive ...
Страница 4: ......
Страница 20: ...20 Safety instructions ...
Страница 34: ...34 Operation principle and hardware description ...
Страница 42: ...42 Planning the cabinet installation ...
Страница 60: ...60 Planning the electrical installation ...
Страница 126: ...126 Using the control panel ...
Страница 318: ...318 Maintenance ...
Страница 334: ...334 The Safe torque off function ...
Страница 338: ...338 Mains chokes ...
Страница 342: ...342 EMC filters ...
Страница 348: ...Dimension drawings 348 Frame size B D1 D2 W H1 H2 ...
Страница 349: ...Dimension drawings 349 ...
Страница 350: ...Dimension drawings 350 Frame size C D1 D2 H2 H1 W ...
Страница 351: ...Dimension drawings 351 ...
Страница 352: ...Dimension drawings 352 Frame size D ...
Страница 354: ...354 Dimension drawings EMC filters JFI 0x ...
Страница 356: ...356 Dimension drawings Brake resistors JBR xx ...
Страница 358: ...358 Dimension drawings ...
Страница 360: ...Contact us www abb com drives www abb com drivespartners 3AXD50000036355 Rev B EN EFFECTIVE 2016 11 21 ...