ID*
From
To
Description
(25)
RUN (module
passivation with
a command)
INIT
Powering off/on
(26)
RUN (module
passivation with
a command)
RUN (ok)
n
No module error
n
Command activate_FV_C = 0
(27)
RUN (channel
passivation &
reintegration)
RUN (module
passivation)
PROFIsafe watchdog, PROFIsafe communication
error or undervoltage/overvoltage was detected.
Note:
In this transition, it is possible that
WD_timeout bit of PROFIsafe F-Host instance
toggles if watchdog timeout is periodically recog-
nized by the Safety I/O module.
(28)
RUN (channel
passivation &
reintegration)
RUN (module
passivation with
a command)
“activate_FV_C = 1” command was sent from the
PROFIsafe F-Host stack
(29)
RUN (user
acknowledge-
ment request)
RUN (channel
passivation and
reintegration)
This transition is possible only if channel error
was identified before or during module passiva-
tion. As a result, after module reintegration one of
the channel tests directly brings Safety I/O
module to RUN (channel passivation & reintegra-
tion state).
(30)
RUN (module
passivation)
RUN (ok)
If the threshold shut-down value was not reached
during undervoltage phase and the process
voltage is back in the normal range, the Safety
I/O module reintegrates and goes to RUN (ok)
state automatically.
If the threshold fuse value was not reached
during overvoltage phase and the process
voltage is back in the normal range, the Safety
I/O module reintegrates and goes to RUN (ok)
state automatically.
(31)
RUN (module
passivation)
RUN (module
passivation)
If process undervoltage event was detected two
times within 1 second, then the Safety I/O module
remains in RUN (module passivation) state.
(32)
RUN (module
passivation with
a command)
RUN (channel
passivation and
reintegration)
This transition is possible only if channel error
was identified during RUN (module passivation
with a command) state. As a result, after com-
mand activate_FV_C = 0, Safety I/O module goes
to RUN (channel passivation & reintegration
state).
* Numbers are transitions in
Ä
Ä
AC500-S Safety Modules
Generic Safety I/O module behaviour > Safety I/O module states
30.03.2017
AC500-S
69