The application program developer must implement a specific fault reaction, e.g., setting safety output chan-
nels to de-energized (‘0’ state), when required.
2.13.2
Safety module with safety input channels (DI581-S, DX581-S and AI581-S)
The safety function of safety modules (DI581-S, DX581-S and AI581-S) with digital and analog input chan-
nels is to correctly read external analog and/or digital signals. If this function cannot be correctly executed,
the safety module or only its input channel, depending on the fault scope, has to go to a safe state. In case
of a channel fault, the safe value (de-energized = ‘0’) is transferred to the safety logic module (e.g., SM560-
S) with additional information about the fault for the given channel.
In case of module fault, no valid telegrams are generated by the safety module to the safety logic module.
The values of those safety input channels will be assigned to safe values (de-energized = ‘0’) on the Safety
CPU.
Faults in the cyclic communication between the Safety CPU and the safety modules are detected by the
safety modules with input channels. If a communication fault occurs, all inputs of the affected safety module
go to a so-called passivation state in which ‘0’ values are sent as process values when the communication to
the Safety CPU is re-established. The switch-over (reintegration) from safety values ‘0’ to process data takes
place only after user acknowledgment.
2.13.3
Safety module with safety output channels (DX581-S)
The safety function of safety modules (DX581-S) with safety output channels is to correctly write their output
channel signals. If this function cannot be correctly executed, the safety module or its output channel group,
depending on the fault scope, has to go to a safe state. In case of a channel fault, the safe value (de-ener-
gized = ‘0’) is set for the given safety output channels. In case of module fault, no valid telegrams are gener-
ated by the safety output module to the Safety CPU. The values of all safety output channels will be
assigned to safe values (de-energized = ‘0’).
Faults in the cyclic communication between the Safety CPU and the safety output modules are detected by
the safety output module DX581-S. If a communication fault occurs, all outputs of the affected safety output
module are de-energized = ‘0’. The switch-over (reintegration) from safety values ‘0’ to process data takes
place only after user acknowledgment, when the communication is re-established.
2.14 Safety function test
After creating a safety program and system configuration, you must carry out a complete function test in
accordance with your automation task. For changes made to a safety program which has already undergone
a complete function test, only the changes need to be tested, if a proper impact analysis was done before.
Safety application program, Safety I/O configuration, etc. have to be verified, printed out and saved for
project data report and archive. The system acceptance test shall follow safety function test. After you finish
configuring the hardware and assigning parameters for the Safety CPU and Safety I/O modules, you can
perform an acceptance test. During the system acceptance test, all relevant application-specific standards
must be adhered.
Overview of AC500-S Safety PLC
Safety function test
30.03.2017
AC500-S