Table 72: FB Name: SF_MutingPar_2Sensor
Name
Data Type
Initial Value
Description, Parameter Values
VAR_INPUT
Activate
BOOL
FALSE
Table 31 “General Input Parameters”
S_AOPD_In
BOOL
FALSE
Variable.
OSSD signal from AOPD.
FALSE: Protection field interrupted.
TRUE: Protection field not interrupted.
S_MutingSwitch11 BOOL
FALSE
Variable.
Status of Muting sensor 11.
FALSE: Muting sensor 11 not actuated.
TRUE: Workpiece actuates muting sensor 11.
S_MutingSwitch12 BOOL
FALSE
Variable.
Status of Muting sensor 12.
FALSE: Muting sensor 12 not actuated.
TRUE: Workpiece actuates muting sensor 12.
S_MutingLamp
BOOL
FALSE
Variable or constant.
Indicates operation of the muting lamp.
FALSE: Muting lamp failure.
TRUE: Muting lamp no failure.
MutingEnable
BOOL
FALSE
Variable or constant.
Command by the control system that enables the
start of the muting function when needed by the
machine cycle. After the start of the muting func-
tion, this signal can be switched off.
FALSE: Muting not enabled
TRUE: Start of Muting function enabled
S_StartReset
BOOL
FALSE
Table 31 “General Input Parameters”
Reset
BOOL
FALSE
Table 31 “General Input Parameters”
DiscTimeEntry
TIME
T#0s
Constant 0..4 s;
Max. discrepancy time for S_MutingSwitch11 and
S_MutingSwitch12 entering muting gate
MaxMutingTime
TIME
T#0s
Constant 0..10 min;
Maximum time for complete muting sequence,
timer started when first muting sensor is actuated.
VAR_OUTPUT
Configuration and programming
AC500-S Libraries > SafetyBlocks_PLCopen_AC500_v22.lib
30.03.2017
AC500-S
360