Output_Value:
0
➔
Not used
128
➔
Used
Compare calculated
Dec_OutputChannel0
(
Ä
step 7
) with
“Output 0, channel configuration”.
They
have to be equal.
If they are not equal, stop the procedure and re-do the configuration and comparison.
If after the second iteration, there is still a difference between those values, stop verification procedure
and contact ABB technical support.
7.
Repeat step 6 for the rest of digital output channels (Channel 1, Channel 2, … Channel 7).
Checklists for AC500-S Commissioning
Verification procedure for safe iParameter setting in AC500-S Safety I/Os > Verification tables for iParameter settings in AC500-S
Safety I/Os
30.03.2017
AC500-S