![ABB AC500-S Скачать руководство пользователя страница 128](http://html.mh-extra.com/html/abb/ac500-s/ac500-s_safety-user-manual_2916128.webp)
Process supply voltage UP
Data
Value Unit
Connections Terminals 1.8 … 4.8 (UP)
+24 V
Connections Terminals 1.9 … 4.9 (ZP)
0 V
Rated value (– 15 %, +20 %, without ripple)
24 V DC
Max. ripple
5 %
Protection against reversed voltage
yes
Rated protection fuse for UP (fast)
10 A
Electrical isolation
per module
Mechanisms in which I/Os are processed
periodically refreshed
Current consumption from UP at normal operation with + 24 V
DC (for module electronics)
0.18 A
Inrush current from UP at 30 V (at power up)
0.1 A
2
s
Inrush current from UP at 24 V (at power up)
0.06 A
2
s
NOTICE!
All DX581-S channels (including test pulse outputs) are protected against reverse polarity, reverse
supply, short circuit and continuous overvoltage up to 30 V DC.
Mounting position
Horizontal or vertical with derating (output load reduced to 50 % at +40 °C per group and with maximal oper-
ating temperature reduced to +40 °C).
Cooling
The natural convection cooling must not be hindered by cable ducts or other parts in the switchgear cabinet.
AC500-S Safety Modules
DX581-S digital safety input/output module > Technical data
30.03.2017
AC500-S
128