LED
Description
Colour
Status
Meaning
DIAG
Diagnostics
Yellow
ON
Configuration error
BLINKING
Not applicable
OFF
No configuration error
RUN
Run mode indi-
cator
Green
ON
Safety CPU is in RUN (Safety) mode. The
application program is executed.
BLINKING
Not applicable
OFF
Safety CPU is in DEBUG STOP mode. The
application program is not executed.
Yellow
ON
Safety CPU is in DEBUG RUN (Non-safety)
mode. The application program is executed.
BLINKING
Firmware, boot project or boot code update
indication
OFF
Safety CPU is in DEBUG STOP mode. The
application program is not executed.
I-ERR
Internal device
error indicator
Red
ON
Internal device error leading to a SAFE STOP
state (no valid telegrams are generated by the
device)
BLINKING
Firmware or boot code update
OFF
No internal device error leading to a safe state
E-ERR
External error
indicator
Red
ON
This LED can be set only from the user applica-
tion program using a special library POU
“AC500-S Libraries” on page 224
details). One of possible use cases is the visu-
alization of important external device errors.
BLINKING
This LED can be set only from the user applica-
tion program using a special library POU
“AC500-S Libraries” on page 224
details). One of possible use cases is the visu-
alization of light external device errors.
OFF
No external errors were identified.
DANGER!
The safety functionality and, as a result, safe process operation, is no more guaranteed by the
SM560-S Safety CPU in the DEBUG RUN (Non-safety) mode.
In case of DEBUG RUN (Non-safety) mode activation on SM560-S Safety CPU,
the responsibility
for safe process operation lies entirely with the organisation and person
responsible for the acti-
vation of DEBUG RUN (Non-safety) mode.
With the help of POU SF_SAFETY_MODE (
Chapter 4.6 “AC500-S Libraries” on page 224
for fur-
ther details) one can retrieve the information if SM560-S is in SAFETY or DEBUG (NON-SAFETY)
mode and, if required, stop or limit user application program execution.
AC500-S Safety Modules
SM560-S Safety CPU > Diagnosis and LED status display
30.03.2017
AC500-S
41