Muting condition 44 (to 8414) (MS_12 is the first exit switch actuated). Start timer DiscTime11_12:
MS_21 AND MS_22 AND NOT MS_11 AND R_TRIG at MS_12
Muting condition 45 (from 8114) (MS_12 is the second exit switch actuated). Stop timer DiscTime11_12:
MS_21 AND MS_22 AND MS_11 AND R_TRIG at MS_12
Muting condition 45 (from 8414) (MS_11 is the second exit switch actuated). Stop timer DiscTime11_12:
MS_21 AND MS_22 AND R_TRIG at MS_11 AND MS_12
Muting condition 15 (one of the exit switches released). Stop timer MaxMutingTime:
NOT MS_21 AND NOT MS_22 AND (F_TRIG at MS_11 OR F_TRIG at MS_12)
Wrong Muting Sequences:
State 8000 - (MutingEnable = FALSE when muting sequence starts) OR
((MS_11 OR MS_12) AND (MS_21 OR MS_22)) OR
(R_TRIG at MS_11 AND MS_12 AND NOT R_TRIG at MS_12) OR
(R_TRIG at MS_12 AND MS_11 AND NOT R_TRIG at MS_11) OR
(R_TRIG at MS_21 AND MS_22 AND NOT R_TRIG at MS_22) OR
(R_TRIG at MS_22 AND MS_21 AND NOT R_TRIG at MS_21) OR
((MS_11 AND NOT R_TRIG at MS_11) AND (MS_12 AND NOT R_TRIG at MS_12)) OR
((MS_21 AND NOT R_TRIG at MS_21) AND (MS_22 AND NOT R_TRIG at MS_22))
State 8011 - NOT MutingEnable OR NOT MS_11 OR MS_21 OR MS_22
State 8311 - NOT MutingEnable OR NOT MS_12 OR MS_21 OR MS_22
State 8012 - NOT MS_11 OR NOT MS_12
State 8021 - R_TRIG at MS_11 OR R_TRIG at MS_12 OR R_TRIG at MS_21 OR R_TRIG at MS_22
State 8014 - NOT MS_11 OR NOT MS_12 OR NOT MS_21
State 8314 - NOT MS_11 OR NOT MS_12 OR NOT MS_22
State 8122 - NOT MutingEnable OR MS_11 OR MS_12 OR NOT MS_21
State 8422 - NOT MutingEnable OR MS_11 OR MS_12 OR NOT MS_22
State 8121 - NOT MS_21 OR NOT MS_22
State 8112 - R_TRIG at MS_11 OR R_TRIG at MS_12 OR R_TRIG at MS_21 OR R_TRIG at MS_22
State 8114 - NOT MS_21 OR NOT MS_22 OR NOT MS_11
State 8414 - NOT MS_21 OR NOT MS_22 OR NOT MS_12